Ordinary local ventilation fan: consists of a collector, a primary host, a secondary host, an outlet silencer, etc. (as shown in Figure 1)
Figure 1: Ordinary local ventilation fan
FBD Series Product Introduction
1. Overview
The FBD series of explosion-proof, pressure-inlet, contra-rotating axial flow local ventilation fans (hereinafter referred to as ventilation fans) comply with the standards MT222-2007 "Technical Conditions for Contra-rotating Local Ventilation Fans" and Q/YAF001-2011 "FBD Series Mine Explosion-proof Pressure-inlet Contra-rotating Axial Flow Local Ventilation Fans". They are suitable for local ventilation in underground coal mines containing methane gas or coal dust and other explosive hazardous environments, and are used with positive pressure ventilation ducts. They can also be used as ventilation equipment for tunnel construction. Details are as follows:
(1) The ventilation fan uses computational fluid dynamics for multi-objective overall optimization design. The blades use aviation engine FMIA airfoil, resulting in a large area of high-efficiency operating conditions. The ventilation fan features compact structure, large air volume, high air pressure, long air delivery distance, high efficiency, energy saving, and low noise.
(2) The ventilation fan is directly driven by two YBF2 series explosion-proof motors for fan use. To extend the service life of the fan, SKF series bearings from Sweden are used for the motor bearings. (Add bearing photo)
(3) According to the different needs of users, there are 3 types of silencers to choose from;
a) Ordinary outlet silencer; (Add photo)
b) Inlet and outlet combined silencer; (Add photo)
c) Side inlet, inlet and outlet combined silencer. (Add photo)
The third type (c) of combined silencer adds a side inlet component, which changes the airflow direction of the inlet without affecting the air intake, refracts the noise, and cooperates with the inlet and outlet silencers to significantly reduce the noise. Testing by the National Mine Equipment Testing Center shows that the noise level is 20-30 decibels lower than that of ordinary ventilation fans.
(4) The explosion-proof type of the ventilation fan and motor is: explosion-proof, and the explosion-proof mark is: ExdbI.
(5) The operating voltage is 380V/660V, 660V/1140V, and does not exceed ±5% of the rated value, and the voltage frequency is 50HZ.
For ventilation fans used underground, the roadway air supply volume should be greater than the maximum operating air volume of the ventilation fan.
The foundation for installing the ventilation fan should be firm and free from dripping water. The height of the edge of the ventilation fan inlet from the ground or top wall should be no less than 0.3m.
The ventilation duct used should be able to withstand the highest pressure of the ventilation fan, and the diameter of the ventilation duct should not be less than the diameter of the impeller.
(6) Service Life
Service life is no less than 5 years, and the safe operating time before the first overhaul is no less than 13000 hours.
2. Structural Features, Working Principle and Technical Parameters
(1) The ventilation fan consists of a collector, motor, primary fan, secondary fan, motor, silencer, etc. (Figure 1 with ordinary silencer; Figure 2 with inlet and outlet silencers; Figure 3 with side inlet combined silencer). The ventilation fan shell structural parts are all welded from steel plates, the inner cylinder is welded from perforated steel plates, lined with sound-absorbing material, and the motor is connected to the air duct by flange joints with bolts. The motor shell and perforated steel plate serve as the inner air duct, and the two impellers rotate contra-rotating at the same speed.
(2) Working Principle
The ventilation fan is driven by two explosion-proof motors of the same capacity and model, respectively driving the first and second impellers. The rotation directions of the two impellers are contra-rotating. Air enters the first impeller, obtains energy, and is discharged through the second impeller. The second impeller also has the function of the stationary blades in an ordinary axial flow fan. While obtaining the straightened circumferential velocity component, it also adds energy to the airflow, thus achieving the high efficiency and high air pressure that ordinary axial flow fans cannot achieve.
(3) Technical parameters of the ventilation fan are shown in Figures 1-3
Figure 1 Ventilation fan structural diagram (with ordinary silencer)
1. Collector, 2. Motor, 3. Primary host, 4. Primary impeller, 5. Secondary impeller, 6. Secondary host, 7. Outlet silencer
Machine Number
Motor Model
Power (kW)
Air Volume m³/min
Air Pressure (Pa)
L1
L3
L
Ф1
Ф2
A
B
h
H
Total Weight kg
4.0
YBF₂90L-2
2×2.2
200-110
300-1800
80
500
1680
490
410
400
280
310
740
280
YBF₂112M-2
2×4
220-120
350-2200
5.0
YBF₂132S-2
2×5.5
230-130
400-2750
120
580
1980
620
510
530
420
390
920
400
YBF₂132S-2
2×7.5
280-170
600-3200
6.0
YBF₂160M-2
2×11
380-220
700-3800
130
740
2340
740
610
700
580
410
1000
600
YBF₂160L-2
2×15
430-260
720-4300
6.3
YBF₂160L-2
2×18.5
500-350
750-4800
140
750
2370
780
640
720
600
435
1035
800
YBF₂180ML-2
2×22
550-360
850-5000
7.1
YBF₂200L-2
2×30
630-380
900-5900
150
840
2570
890
730
750
630
495
1145
1000
YBF₂200L-2
2×37
680-400
950-6100
8.0
YBF₂225M-2
2×45
780-440
1050-7500
160
1020
3000
950
820
800
680
530
1250
1450
YBF₂250M-2
2×55
900-540
1100-7800
YBF₂280S-2
2×75
1010-600
1600-8400
Figure 2 Ventilation fan structure diagram (with inlet and outlet silencers)
1. Current collector, 2. Inlet silencer, 3. Motor, 4. Primary main unit, 5. Primary impeller, 6. Secondary impeller, 7. Secondary main unit, 8. Outlet silencer
Machine Number
Motor Model
Power kW
Air Volume m³/min
Air Pressure Pa
L1
L2
L3
L
Ф1
Ф2
A
B
h
H
Total Weight kg
4.0
YBF₂90L-2
2×2.2
200-110
300-1800
80
600
500
2280
490
410
400
280
310
740
350
YBF₂112M-2
2×4
220-120
350-2200
5.0
YBF₂132S-2
2×5.5
230-130
400-2750
120
700
580
2680
620
510
530
420
390
920
480
YBF₂132S-2
2×7.5
280-170
600-3200
6.0
YBF₂160M-2
2×11
380-220
700-3800
130
730
740
3070
740
610
700
580
410
1000
700
YBF₂160L-2
2×15
430-260
720-4300
6.3
YBF₂160L-2
2×18.5
500-350
750-4800
140
730
750
3100
780
640
720
600
435
1035
920
YBF₂180ML-2
2×22
550-360
850-5000
7.1
YBF₂200L-2
2×30
630-380
900-5900
150
740
840
3310
890
730
750
630
495
1145
1150
YBF₂200L-2
2×37
680-400
950-6100
8.0
YBF₂225M-2
2×45
780-440
1050-7500
160
800
1020
3800
950
820
800
680
530
1250
1600
YBF₂250M-2
2×55
900-540
1100-7800
YBF₂280S-2
2×75
1010-600
1600-8400
Figure 3 Ventilation fan structure diagram (with side-entry combined silencer)
1. Side-entry device, 2. Current collector, 3. Inlet silencer, 4. Motor, 5. Primary main unit, 6. Primary impeller, 7. Secondary impeller, 8. Secondary main unit, 9. Outlet silencer
Machine Number
Motor Model
Power kW
Air Volume m³/min
Air Pressure Pa
L1
L2
L3
L
Ф1
Ф2
A
B
h
H
Total Weight kg
4.0
YBF₂90L-2
2×2.2
200-110
300-1800
80
600
500
2580
490
410
400
280
310
740
380
YBF₂112M-2
2×4
220-120
350-2200
5.0
YBF₂132S-2
2×5.5
230-130
400-2750
120
700
580
3010
620
510
530
420
390
920
520
YBF₂132S-2
2×7.5
280-170
600-3200
6.0
YBF₂160M-2
2×11
380-220
700-3800
130
730
740
3420
740
610
700
580
410
1000
750
YBF₂160L-2
2×15
430-260
720-4300
6.3
YBF₂160L-2
2×18.5
500-350
750-4800
140
730
750
3480
780
640
720
600
435
1035
970
YBF₂180ML-2
2×22
550-360
850-5000
7.1
YBF₂200L-2
2×30
630-380
900-5900
150
740
840
3710
890
730
750
630
495
1145
1200
YBF₂200L-2
2×37
680-400
950-6100
8.0
YBF₂225M-2
2×45
780-440
1050-7500
160
800
1020
4250
950
820
800
680
530
1250
1680
YBF₂250M-2
2×55
900-540
1100-7800
YBF₂280S-2
2×75
1010-600
1600-8400
3. Installation and Debugging
(1) Before assembly, the radial clearance between the blade tip and the inner casing must be checked. The radial clearance should be between 1.5‰ and 3.5‰ of the impeller diameter, and not less than 1mm; no axial clearance is allowed after the assembly of each casing.
(2) The rotation direction of the impeller must conform to the direction indicated by the casing mark.
(3) The ventilation fan must be managed and operated by dedicated personnel.
(4) The installation and use of the ventilation fan must comply with the relevant provisions of the "Coal Mine Safety Regulations", and the internal and external grounding wires must be securely connected as required before operation.
(5) The stripped exposed end of the motor lead wire connection should not exceed 1.5mm, and the motor should be installed according to the requirements of the motor instruction manual. The six terminals in the motor terminal box can be adapted for two different voltages when changing the connection method (see Figure 2). The phase sequence U, V, W of the motor needs to correspond to the phase sequence A, B, C of the external power supply, and the motor rotation direction, viewed from the shaft extension end, should be clockwise, otherwise the motor will reverse.
Figure 2 Motor Wiring Diagram (Note: Motor voltage levels are 380V/660V and 660V/1140V respectively)
4. Use and Operation
(1) Preparation and Inspection Before Use
a) The cold insulation resistance between the motor stator winding and the casing should be measured and must be higher than 50MΩ; if it does not meet the requirements, drying treatment should be performed.
b) Whether there are safety signs and explosion-proof certificate numbers.
c) All flameproof surface parts are free of cracks and defects affecting flameproof performance (new motors that have not been disassembled do not need to be checked).
d) The introduced cable cores must be pressed and fixed with wiring clamps or bowed washers to prevent cable movement.
e) Check whether all fasteners and fittings of the ventilation fan are complete and secure, whether connections are reliable, whether trial operation is flexible, whether there is noise, abnormal sound, or impact sound, whether the impeller rotation direction is correct, and whether the grounding wire is properly connected.
(2) Instructions During Use
a) To ensure the long-term safe operation of the ventilation fan, attention should be paid to correct use and regular maintenance.
b) When starting, turn on the first-stage ventilation fan in sequence, and after 5 seconds of operation, start the second-stage ventilation fan.
c) During operation, frequently check whether the sound is normal and whether there is any looseness at the connections.
d) Motor maintenance should be carried out according to the provisions in the motor instruction manual.
e) The motor bearings should be inspected at least once every 6 months of operation. If the bearing grease is found to be deteriorated or leaking, it must be replaced in time. Before replacement, the bearings must be cleaned with gasoline. ZL-3 lithium-based grease (Sy142-75) should be used, with the filling amount being 1/2 of the net empty volume of the bearing chamber. (For 180000 series sealed bearings, grease does not need to be replaced during their service life)
f) The bearing clearance during use should be within the allowable range, the bearing temperature during operation should not exceed the allowable value, and the sound should be normal. If bearings are worn or damaged, new bearings should be replaced.
g) If the motor becomes damp, it must be dried.
h) After a period of use, the silencing holes may become blocked by coal dust, necessitating cleaning with high-pressure airflow to prevent increased fan noise.
i) Inspect the ventilation fan monthly, checking all components.
j) When not in use, the ventilation fan should be stored in a well-ventilated, dry location to prevent moisture damage and other losses.
5. Fault Analysis and Troubleshooting
Table 1 Main Faults and Troubleshooting Methods
Fault Characteristics
Fault Causes
Fault Identification and Troubleshooting Methods
Metallic collision sound inside the ventilation fan
Blade rubbing against the casing
Replace the blade or casing
Metal objects entering
Remove foreign objects
Motor bearing damage
Replace the motor or bearing
Whistling sound from the bearing (accompanied by temperature increase)
Excessive, insufficient, or unclean lubricating grease
Reduce or add lubricating grease or clean the bearing
Lubricating grease aging or incorrect type
Replace the lubricating grease
Bearing vibration and internal collision sound
Excessive lubricating oil or bearing fatigue and wear
Reduce lubricating grease or replace the bearing
Ventilation fan and motor vibration
Impeller imbalance
Replace the impeller
Insufficient foundation hardness and damage
Check the foundation
Loose flange connection bolts
Check all connection bolts
Insufficient pressure or air volume
Air duct leakage or insufficient motor speed
Check for air leaks or check the motor
Increased vibration, intermittent noise
Ventilation fan operating under unstable conditions
Check the ventilation fan intake and exhaust conditions
One or two stages of the ventilation fan stop running
Motor damage or power failure
Replace the motor or reconnect the power
Humming sound when power is turned on but not running
Incorrect phase sequence of the motor
Swap any two power lines
Difficult ventilation fan startup
Low power voltage or starter malfunction
Increase power voltage or check the starter
6. Precautions for Ventilation Fan Use
When using a ventilation fan underground in a coal mine, strictly adhere to the relevant regulations in the "Coal Mine Safety Regulations":
(1) The mining face using the ventilation fan must not be stopped. If the ventilation is stopped due to power failure for maintenance, personnel must be evacuated and the power must be cut off.
(2) Before resuming ventilation, gas must be checked. Only when the gas concentration in the airflow within 10 meters of the ventilation fan and its switch does not exceed 0.5% can the local ventilation fan be manually started.
(3) If the ventilation fan stops running for any reason, before resuming ventilation, gas must be checked first. Only when the highest gas concentration in the stopped ventilation area does not exceed 1.0% and the highest carbon dioxide concentration does not exceed 1.5%, and the conditions in point 2 are met, can the ventilation fan be manually started to resume normal ventilation.
(4) When using a counter-rotating axial flow fan, both sets of impellers must be started simultaneously. If one motor is damaged, the entire unit must be stopped for maintenance, and single-stage startup is not permitted.